PE-14(1): Automatic Controls

PE-14(1): Automatic Controls requires you to deploy automated environmental controls in your facilities to prevent temperature, humidity, water, smoke, and related fluctuations from damaging systems and data-processing equipment. To operationalize it quickly, define acceptable environmental ranges, implement automatic control/monitoring with alerts, and retain evidence that controls are configured, tested, and continuously monitored. (NIST SP 800-53 Rev. 5 OSCAL JSON)

Key takeaways:

  • Scope the “facility” boundary first (data center, server rooms, comms closets, and any third-party colocation spaces you rely on).
  • Automatic controls must be configured to prevent harmful fluctuations, not just detect them.
  • Audit readiness depends on tight evidence: configuration, monitoring logs, testing, and corrective actions. (NIST SP 800-53 Rev. 5 OSCAL JSON)

The pe-14(1): automatic controls requirement sits in the Physical and Environmental Protection (PE) family and focuses on a simple operational outcome: your systems should not be taken down, degraded, or physically damaged by environmental conditions in the facility. That means you need more than a policy that says “we maintain HVAC.” You need automated environmental controls (and the operational muscle around them) that keep conditions within safe parameters, generate actionable alerts, and support fast response when conditions drift.

For most organizations, the hard part is not buying sensors or building automation. The hard part is scoping which spaces count, aligning responsibilities across Facilities, IT, and Security, and proving control operation with evidence that an assessor can follow end-to-end. If your systems run in colocation or cloud-adjacent cages, you also need third-party due diligence artifacts that show environmental controls exist and are monitored.

This page translates PE-14(1) into requirement-level implementation steps you can hand to an owner and verify quickly, with a focus on artifacts and common audit hangups. (NIST SP 800-53 Rev. 5)

Regulatory text

Excerpt (PE-14(1)): “Employ the following automatic environmental controls in the facility to prevent fluctuations potentially harmful to the system: {{ insert: param, pe-14.01_odp }}.” (NIST SP 800-53 Rev. 5 OSCAL JSON)

Operator interpretation: You must implement automated mechanisms that control environmental conditions in the facility so they do not drift into ranges that could harm system components or interrupt operations. The control is outcome-driven: “prevent fluctuations potentially harmful to the system.” (NIST SP 800-53 Rev. 5 OSCAL JSON)

What “{{ insert: param, pe-14.01_odp }}” means in practice: In the OSCAL representation, that placeholder indicates organization-defined parameters (ODPs). Your job is to explicitly define the environmental factors you will automatically control (for example: temperature, humidity, water detection response, smoke/fire suppression actuation signals, power conditioning interfaces) and document the thresholds and actions. Treat this as a required scoping and parameter-setting step, not optional tailoring. (NIST SP 800-53 Rev. 5 OSCAL JSON)

Plain-English requirement interpretation (what you’re being held to)

A compliant implementation has four properties:

  1. Defined “safe operating ranges” for relevant environmental conditions for each covered space (or for each class of space), based on equipment needs and uptime expectations.
  2. Automatic controls that actively maintain conditions (HVAC control loops, humidification/dehumidification controls, automated dampers, automatic transfer/switchover logic, automated shutdown or isolation actions where appropriate).
  3. Continuous monitoring and alerting so the right on-call group knows before conditions become harmful.
  4. Evidence of operation: configurations, monitoring outputs, tests, and incident/corrective-action records that show the controls actually work. (NIST SP 800-53 Rev. 5 OSCAL JSON)

Who it applies to (entity and operational context)

Entity types: This requirement commonly applies to federal information systems and contractor systems that handle federal data where NIST SP 800-53 is in scope. (NIST SP 800-53 Rev. 5)

Operational contexts where assessors press hardest

  • Owned or leased facilities with dedicated data centers or server rooms.
  • Distributed sites: branch offices with IDF/MDF closets, network racks, telecom rooms, lab spaces with specialized equipment.
  • Colocation / managed data center environments (third party facilities) where you still need assurance and evidence, even if the third party runs the building systems.
  • Mixed cloud/on-prem where key network/security appliances remain on-prem and can be impacted by HVAC or water intrusion.

Systems boundary note: PE-14(1) is facility-focused, but scoping usually follows where “system components supporting the system” reside. If your “system” boundary includes on-prem network/security gear, the rooms housing that gear are in scope. (NIST SP 800-53 Rev. 5)

What you actually need to do (step-by-step)

Use this as an implementation runbook.

1) Define scope: facilities and spaces in scope

  • Build an inventory of spaces that house in-scope system components: data centers, server rooms, comms closets, secure rooms, and any colocation cages.
  • Record for each space: address, access constraints, equipment types, and the Facilities/IT owner split.
  • Decide and document exclusions explicitly (for example: user work areas with no system components).

Deliverable: “In-scope facility spaces register” mapped to the system boundary. (NIST SP 800-53 Rev. 5 OSCAL JSON)

2) Define organization parameters (ODPs): what you will automatically control

Because the control text uses an organization-defined insertion, you need a documented parameter set that includes:

  • Environmental factors covered (temperature, humidity, water, smoke, etc.)
  • Acceptable ranges/thresholds per space type
  • Required automated actions when thresholds are crossed (increase cooling, activate dehumidifier, send alarm, trigger building management escalation, isolate zone, initiate safe shutdown where appropriate)
  • Alert routing and severity rules (who gets paged, who gets ticketed)

Deliverable: “PE-14(1) automatic environmental controls standard” that lists factors, thresholds, and actions. (NIST SP 800-53 Rev. 5 OSCAL JSON)

3) Implement or validate automatic controls (not just sensors)

For each in-scope space, confirm you have:

  • A control system capable of automatic adjustment (often a BMS/BAS integrated with HVAC and environmental sensors)
  • Redundancy or fail-safe behavior appropriate to your risk (document what happens on controller failure, sensor failure, or loss of communications)
  • Calibrated sensors and defined maintenance intervals (document the interval; the control does not mandate a specific cadence)
  • Power resilience for the monitoring/control path where necessary (for example: UPS-backed controllers)

Evidence focus: configuration exports, control diagrams, and work orders that show the control is in place and maintained. (NIST SP 800-53 Rev. 5 OSCAL JSON)

4) Establish monitoring, alerting, and response procedures

Automatic controls reduce risk, but auditors will still ask “how do you know it’s working today?”

  • Centralize alarms (BMS console, SIEM ingestion, ticketing integration, or on-call paging)
  • Define response playbooks: water alarm, HVAC failure, high temp, humidity out-of-range
  • Set ownership: Facilities responds to mechanical faults; IT responds to equipment protection steps; Security coordinates if physical incident

Deliverables:

  • Alarm routing matrix (alarm type → responder → escalation)
  • Incident playbooks and on-call rosters (or shared duty schedules)
  • Sample alerts and tickets showing closure and corrective action. (NIST SP 800-53 Rev. 5 OSCAL JSON)

5) Test the controls and document results

Assessors look for evidence that controls are not theoretical.

  • Perform functional tests appropriate to each control type (alarm tests, simulated threshold crossings, failover tests if supported)
  • Record outcomes, issues found, and remediation
  • Retest after material changes (HVAC replacement, BMS update, room remodel)

Deliverable: environmental controls test records and corrective action tracking. (NIST SP 800-53 Rev. 5 OSCAL JSON)

6) Close the third-party loop (colocation and managed facilities)

If a third party operates the facility controls:

  • Contractually require environmental control and monitoring commitments (or obtain the provider’s control description)
  • Obtain evidence (attestations, audit reports, or provider documentation) that maps to your PE-14(1) parameters
  • Define how you receive incident notifications and how quickly

Practical tip: If your provider will not share raw BMS logs, document compensating evidence such as incident notifications, service reports, and formal attestations tied to your thresholds. Keep it consistent with your ODPs. (NIST SP 800-53 Rev. 5 OSCAL JSON)

7) Make it assessable: map ownership, procedures, and recurring evidence

Operationalize the control as a standing compliance object:

  • Name the control owner (often Facilities or Physical Security with IT as a key stakeholder)
  • Document the procedure: monitoring review, alarm response, maintenance, testing
  • Define recurring evidence: monthly alarm summaries, maintenance tickets, calibration records, test reports

Where Daydream fits: Daydream helps you map PE-14(1) to a control owner, an implementation procedure, and recurring evidence artifacts so assessments do not turn into a scavenger hunt across Facilities, IT, and third parties. (NIST SP 800-53 Rev. 5 OSCAL JSON)

Required evidence and artifacts to retain

Keep artifacts in a single, assessor-friendly folder structure by site and by control.

Core artifacts

  • PE-14(1) parameter standard (factors, thresholds, automated actions) (NIST SP 800-53 Rev. 5 OSCAL JSON)
  • In-scope facility spaces register and ownership mapping (NIST SP 800-53 Rev. 5 OSCAL JSON)
  • Architecture/diagrams: HVAC/BMS overview, sensor placement map, alarm flow (NIST SP 800-53 Rev. 5)
  • Configuration evidence: BMS/BAS settings exports or screenshots, setpoints, alarm thresholds (NIST SP 800-53 Rev. 5 OSCAL JSON)
  • Monitoring evidence: alarm logs, alert notifications, tickets, trend reports (NIST SP 800-53 Rev. 5 OSCAL JSON)
  • Maintenance evidence: preventive maintenance schedules, work orders, calibration certificates where applicable (NIST SP 800-53 Rev. 5 OSCAL JSON)
  • Testing evidence: functional test plans, results, issue remediation, retest results (NIST SP 800-53 Rev. 5 OSCAL JSON)
  • Third-party evidence for colocation: contract clauses, provider documentation/attestations, incident communications (NIST SP 800-53 Rev. 5)

Common exam/audit questions and hangups

Questions you should be ready to answer

  • “Which spaces are in scope, and why?” Bring the spaces register and system boundary rationale. (NIST SP 800-53 Rev. 5)
  • “Show me the automatic part.” Be ready to demonstrate control loops, automated setpoint changes, and automated alerting, not just sensors on a dashboard. (NIST SP 800-53 Rev. 5 OSCAL JSON)
  • “What thresholds are you using, and who approved them?” Provide your ODP document and change history. (NIST SP 800-53 Rev. 5 OSCAL JSON)
  • “Show a real event.” Provide a recent alarm ticket with timestamps, response, and resolution notes. (NIST SP 800-53 Rev. 5 OSCAL JSON)
  • “How do you know the alarms work?” Show test records and maintenance evidence. (NIST SP 800-53 Rev. 5 OSCAL JSON)
  • “What about your colocation provider?” Show your assurance package and notification process. (NIST SP 800-53 Rev. 5)

Hangups

  • Facilities owns the systems, but Security owns the control narrative. Fix this by naming joint owners and defining the evidence supply chain.

Frequent implementation mistakes and how to avoid them

  1. Treating monitoring as control
    Mistake: Only installing sensors and calling it done.
    Fix: Document the automated actions taken when conditions drift, and show configuration evidence. (NIST SP 800-53 Rev. 5 OSCAL JSON)

  2. No organization-defined parameters
    Mistake: Leaving thresholds implicit (“normal room temp”).
    Fix: Create an explicit parameter table per space type, with change control. (NIST SP 800-53 Rev. 5 OSCAL JSON)

  3. Ignoring small spaces
    Mistake: Data center is covered, comms closets are forgotten.
    Fix: Use your network rack inventory and site lists to drive scope. (NIST SP 800-53 Rev. 5)

  4. Evidence trapped in Facilities tools
    Mistake: You cannot produce logs, configs, or test records during an audit window.
    Fix: Set recurring exports and store them in your GRC repository; Daydream can track the required artifacts and owners. (NIST SP 800-53 Rev. 5 OSCAL JSON)

  5. Third-party facility blind spot
    Mistake: Assuming colocation “handles it,” with no proof.
    Fix: Obtain provider documentation mapped to your PE-14(1) parameters and keep incident communications. (NIST SP 800-53 Rev. 5)

Enforcement context and risk implications

No public enforcement cases were provided for this control in the supplied source catalog, so this page does not cite enforcement actions. Practically, PE-14(1) failures show up as availability incidents (overheating shutdowns, water intrusion damage) and as assessment findings tied to weak physical/environmental protection evidence. (NIST SP 800-53 Rev. 5)

Practical execution plan (30/60/90-day)

Use a phased plan without fixed-day promises for completion. Move as fast as your Facilities change windows allow.

First 30 days: scope, ownership, and parameters

  • Confirm in-scope spaces and owners; publish the spaces register.
  • Draft PE-14(1) parameters: factors, thresholds, automated actions, and alert routing.
  • Identify evidence sources per site (BMS exports, ticketing, maintenance records) and set a collection method. (NIST SP 800-53 Rev. 5 OSCAL JSON)

Next 60 days: control validation and evidence pipeline

  • Validate for each site that automatic controls exist and match the parameter standard.
  • Configure alert routing and ticketing; test alarm notifications end-to-end.
  • Start retaining recurring evidence (alarm summaries, maintenance tickets, config snapshots). (NIST SP 800-53 Rev. 5 OSCAL JSON)

Next 90 days: testing maturity and third-party closure

  • Run functional tests and record results; remediate gaps and retest.
  • For colocation/managed sites, collect provider assurance artifacts and align them to your parameters.
  • Standardize the operating procedure and assign recurring control attestations in your GRC workflow (Daydream can manage owners, tasks, and evidence). (NIST SP 800-53 Rev. 5 OSCAL JSON)

Frequently Asked Questions

What counts as “automatic environmental controls” for PE-14(1)?

Automatic controls are mechanisms that actively regulate conditions (like HVAC/BMS control loops, humidification control, automated dampers, or automated alarms tied to response actions), not only sensors. Your evidence should show configured thresholds and system actions when thresholds are crossed. (NIST SP 800-53 Rev. 5 OSCAL JSON)

Do I need to cover every office location?

Cover spaces that house in-scope system components and could experience environmental fluctuations that harm them, such as server rooms and comms closets. Document your scope decisions in a spaces register tied to the system boundary. (NIST SP 800-53 Rev. 5)

How do we handle colocation where we can’t access BMS settings or raw logs?

Document your organization-defined parameters and obtain third-party assurance artifacts that demonstrate equivalent controls and monitoring. Keep incident notifications, service reports, and contractual commitments that map back to your parameters. (NIST SP 800-53 Rev. 5)

What evidence is most persuasive to an assessor?

Configuration proof (setpoints and alarm thresholds), monitoring outputs (alerts/tickets), and test records that show alarms and automated actions work. Pair each artifact with ownership and a retention cadence so it is reproducible. (NIST SP 800-53 Rev. 5 OSCAL JSON)

Can Facilities “own” this control if Security is responsible for NIST compliance?

Yes, but write down a split: Facilities owns operation and maintenance; Security/GRC owns the control statement, evidence requirements, and assessment coordination. A RACI plus an evidence inventory prevents audit delays. (NIST SP 800-53 Rev. 5 OSCAL JSON)

What’s the quickest way to operationalize PE-14(1) in a GRC program?

Start by mapping PE-14(1) to a named owner, a documented procedure, and a list of recurring evidence artifacts. Daydream is designed to track that mapping and keep evidence collection consistent across sites and third parties. (NIST SP 800-53 Rev. 5 OSCAL JSON)

Frequently Asked Questions

What counts as “automatic environmental controls” for PE-14(1)?

Automatic controls are mechanisms that actively regulate conditions (like HVAC/BMS control loops, humidification control, automated dampers, or automated alarms tied to response actions), not only sensors. Your evidence should show configured thresholds and system actions when thresholds are crossed. (NIST SP 800-53 Rev. 5 OSCAL JSON)

Do I need to cover every office location?

Cover spaces that house in-scope system components and could experience environmental fluctuations that harm them, such as server rooms and comms closets. Document your scope decisions in a spaces register tied to the system boundary. (NIST SP 800-53 Rev. 5)

How do we handle colocation where we can’t access BMS settings or raw logs?

Document your organization-defined parameters and obtain third-party assurance artifacts that demonstrate equivalent controls and monitoring. Keep incident notifications, service reports, and contractual commitments that map back to your parameters. (NIST SP 800-53 Rev. 5)

What evidence is most persuasive to an assessor?

Configuration proof (setpoints and alarm thresholds), monitoring outputs (alerts/tickets), and test records that show alarms and automated actions work. Pair each artifact with ownership and a retention cadence so it is reproducible. (NIST SP 800-53 Rev. 5 OSCAL JSON)

Can Facilities “own” this control if Security is responsible for NIST compliance?

Yes, but write down a split: Facilities owns operation and maintenance; Security/GRC owns the control statement, evidence requirements, and assessment coordination. A RACI plus an evidence inventory prevents audit delays. (NIST SP 800-53 Rev. 5 OSCAL JSON)

What’s the quickest way to operationalize PE-14(1) in a GRC program?

Start by mapping PE-14(1) to a named owner, a documented procedure, and a list of recurring evidence artifacts. Daydream is designed to track that mapping and keep evidence collection consistent across sites and third parties. (NIST SP 800-53 Rev. 5 OSCAL JSON)

Operationalize this requirement

Map requirement text to controls, owners, evidence, and review workflows inside Daydream.

See Daydream